Havous.
All tools / Calculators / kW to amps calculator

kW to amps calculator

Kilowatts to amps for single and three phase, with the power factor for motors.

Loadkilowatts and volts
Current–
Apparent power–

How to use it

  1. Type the load in kW and the supply voltage.
  2. Pick single or three phase and set the power factor.
  3. Read the running current and the apparent power.

7.5 kW at 240 V single phase with a factor of 0.9 is 34.7 A.

Questions

What power factor should I use?

Use 1.00 for heaters and lamps, 0.8 to 0.9 for motors, and the figure on the nameplate when you have it.

Is this the breaker size?

No. This is the running current. Breakers are sized above it, and the cable has to match the breaker.

What people use it for

The formulas

Single phase: amps equal kilowatts times 1,000 divided by volts divided by power factor. Three phase: amps equal kilowatts times 1,000 divided by the square root of three divided by volts divided by power factor. The power factor only matters for motors, transformers and other inductive loads; resistive loads like heaters sit at 1.00.

The result is the running current. Motors draw several times that for a moment on start up, so a breaker is normally sized above the running figure and the circuit is sized for the starting current.

LoadSupplyCurrent
1 kW120 V single phase8.3 A
7.5 kW240 V single phase34.7 A
7.5 kW400 V three phase, pf 0.912.0 A
22 kW400 V three phase, pf 0.935.3 A